SF6 Micro-moisture and Density Meter Module (OT-WS01)

The OT-WS01 micro water density module can monitor the moisture, density (P20), temperature, dew point, and other information of SF6 gas in the GIS chamber.

Classification:

The Micro-moisture and Density Analyzer's physical interface is a 4-pin electrical connector, with the pins defined as: V+, V−, A, and B. V+ and V− are the power supply interfaces. The Rated Voltage is DC 12V, with an Allowable Range of DC 5V−24V. DC 12V is the recommended supply voltage. A and B are the RS485 communication interfaces, which connect to the host unit's RS485 port via cable.If the distance between the analyzer and the host unit is long or if electromagnetic interference (EMI) is significant, it is recommended to use Shielded Twisted Pair (STP) cable for connection to ensure data transmission accuracy and stability.

Communication between the Micro-moisture and Density Analyzer and the host unit is conducted via the RS485 interface using the Modbus-RTU protocol.

The Default Baud Rate is 9600 bps, with No Parity, 8 Data Bits, and 1 Stop Bit (N, 8, 1).

Reference Standard: DL/T 506-2018 《Measurement Method for Humidity of Insulating Gas in Sulfur Hexafluoride Electrical Equipment》

Certified Tests

  1. GB/T 2423.1-2008 《Environmental testing for electric and electronic products Part 2: Test methods - Test A: Cold》
  2. GB/T 2423.2-2008 《Environmental testing for electric and electronic products Part 2: Test methods - Test B: Dry heat》
  3. GB/T 2423.3-2016 《Environmental testing Part 2: Test methods - Test Cab: Damp heat, steady state》
  4. GB/T 2423.4-2008 《Environmental testing for electric and electronic products Part 2: Test methods - Test Db: Damp heat, cyclic (12h+12h cycle)》
  5. GB/T 17626.2-2018 《Electromagnetic compatibility - Testing and measurement techniques - Electrostatic discharge immunity test》
  6. GB/T 17626.3-2016 《Electromagnetic compatibility - Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test》
  7. GB/T 17626.8-2006 《Electromagnetic compatibility - Testing and measurement techniques - Power frequency magnetic field immunity test》
  8. GB/T 17626.9-2011 《Electromagnetic compatibility - Testing and measurement techniques - Pulse magnetic field immunity test》

 

Technical Specifications

Monitoring Parameters

Temperature, Pressure, Density (P20),

Dew Point, Atmospheric Dew Point,

Micro-moisture

Communication Method RS485, Modbus-RTU Protocol

Temperature

Measurement Range

-40~85℃
Humidity Measurement Range 0~100%RH Pressure Measurement Range 0~1.4MPa

Density (P20)

Measurement Range

0~1.4MPa

Dew Point Measurement Range

-60~125℃ Atmospheric Dew Point Measurement Range -60~125℃ Micro-moisture
Measurement Range
0-20000ppm
Temperature, Dew Point, Atmospheric Dew Point Resolution 0.1℃ Humidity Resolution 0.1%RH

Pressure, Density (P20)

Resolution

0.001MPa

Micro-moisture

Resolution

1ppm Alarm Type High/Low Pressure Pre-warning and Alarm System Error Range <5%

System Operating

Temperature Range

-40~85℃

System Operating

Pressure Range

0-1.4MPa

System Operating

Humidity Range

0∼95%RH Non condensing